Wire Size for 250 Feet Run

What wire size do you need for a 250 ft run? See the complete wire gauge chart for 15A–200A circuits at 250 ft, keeping voltage drop under 3%. Very long residential/farm run. Consider a sub-panel at the destination to reduce conductor costs.

Wire Size Chart for 250 Feet Run (Copper, 3% Max VD)

Amps120V WireVD%240V WireVD%
15A6 AWG2.5%8 AWG2.0%
20A4 AWG2.1%8 AWG2.6%
30A3 AWG2.5%6 AWG2.5%
40A2 AWG2.6%4 AWG2.1%
50A1 AWG2.6%4 AWG2.6%
60A1/0 AWG2.5%3 AWG2.5%
80A2/0 AWG2.6%2 AWG2.6%
100A3/0 AWG2.6%1 AWG2.6%
150A4/0 AWG3.1%3/0 AWG1.9%
200A4/0 AWG4.1%4/0 AWG2.0%

Based on copper conductors, 75°C rating, 250 ft one-way distance, 3% max voltage drop. Use our Voltage Drop Calculator for exact calculations.

Why Distance Matters for Wire Sizing

At 250 ft, conductor resistance becomes significant. Per NEC 210.19 (FPN No. 4), total voltage drop should not exceed 5% for branch circuits (3% recommended for the branch circuit alone). Very long residential/farm run. Consider a sub-panel at the destination to reduce conductor costs.

The voltage drop formula: VD% = (2 × L × I × R) / (CMA × V) × 100 where L is one-way distance in feet, I is current in amps, R is conductor resistivity (10.37 for copper), CMA is wire area in circular mils, and V is voltage.

Cost Considerations

For 250 ft runs at high amperage, wire cost becomes significant. At this distance, consider installing a sub-panel at the destination — it may be cheaper to run one large feeder than multiple oversized branch circuits.

Disclaimer: Reference only. Verify with a licensed electrician. Ambient temperature derating and conduit fill may require further upsizing.